Requirements and documentation
Passive house calculation: NS 3700 and NS 3701
Passive houses have a very low heating need, achieved with good insulation, few thermal bridges, high air tightness and efficient heat recovery. In Norway, the criteria are set out in NS 3700 for residential buildings and NS 3701 for commercial buildings.
How passive houses differ from TEK17
TEK17 caps the total net energy need. The passive house standards add their own requirements for heating need and heat loss, so the building envelope, not the energy supply, delivers the low demand.
- Requirements for the heat loss coefficient and calculated heating need
- Minimum requirements for windows, air tightness and heat recovery
- Requirements adjusted for building size and the local climate
NS 3700 and NS 3701
NS 3700:2013 covers residential buildings and NS 3701:2012 commercial buildings, meaning offices, schools and other non-residential buildings. The heating requirement is adjusted for building size and the annual mean temperature at the site, so a small house in a cold inland climate gets different limits than a large apartment block on the coast. Both standards also have a less strict low-energy level.
Documentation
Passive house criteria are documented with an energy calculation under NS 3031, with the additions the standards require. Because the margins are often small, it pays to calculate early and follow up when constructions, windows and ventilation systems change.
How Proff handles it
Passive house and FutureBuilt in the same calculation
Proff checks the NS 3700 passive house criteria for homes directly in the model, in addition to the TEK17 check for small houses.
- NS 3700 for residential buildings
- FutureBuilt criteria for plus houses and nearly zero-energy buildings
- See which requirements are not met, and what it takes
Questions and answers
No, TEK17 does not require passive house level. Many developers, municipalities and programs still set passive house or a similar level as a goal.
Sources and regulations
Always check the current version of regulations and standards before using the numbers in a project.
Read next
Energy requirements in TEK17
Energy frames per building category, minimum requirements and how compliance is documented.
U-value: calculating heat loss in components
U-values layer by layer under NS-EN ISO 6946, and the minimum requirements in TEK17.
Energy simulation for buildings and homes
Dynamic simulation hour by hour and quarter hour by quarter hour: when it gives better answers and how the result is checked.
Spend your time on judgment, not data entry
Proff gathers available building data, reads floor plans and builds an editable model, so you can calculate everything from houses to hospitals without the detours.