U-value: calculating heat loss in components
The U-value tells you how much heat passes through one square meter of a building component when there is one degree of difference between inside and outside. The lower the U-value, the better the construction insulates. It is one of the most important inputs in any energy calculation.
How to calculate the U-value
The U-value is the inverse of the total thermal resistance. The thermal resistance of each layer is its thickness divided by the thermal conductivity of the material. Add the internal and external surface resistances. The calculation method is set out in NS-EN ISO 6946.
- Add up the thermal resistance of each layer, plus the internal and external surface resistance
- Calculate non-uniform layers, such as insulation between studs, with upper and lower limits
- Ground floors are calculated under NS-EN ISO 13370, because the ground also insulates
- Windows and doors have their own U-values from the manufacturer, including the frame
The minimum requirements in TEK17
However the energy frame is met, TEK17 section 14-3 limits how poor individual components can be. The requirements make sure a building does not compensate for weak insulation with an efficient heating system.
Applies to buildings in general. Homes and holiday homes with log outer walls have separate requirements.
| Component | Requirement |
|---|---|
| External wall | U-value at most 0.22 W/(m²K) |
| Roof | U-value at most 0.18 W/(m²K) |
| Floor on ground and toward open air | U-value at most 0.18 W/(m²K) |
| Window and door, including frame | U-value at most 1.2 W/(m²K) |
| Air leakage at 50 Pa | At most 1.5 air changes per hour |
Source: Norwegian Building Authority, TEK17 section 14-3. Check the current text before use.
Thermal bridges come on top
The U-value describes the surface. Where constructions meet, at floor joists, window frames and corners, thermal bridges add extra heat loss. In the energy calculation they are included as a normalized thermal bridge value for the whole building. In a well-insulated building, thermal bridges can make up a large share of the total transmission loss.
How Proff handles it
U-values in the model
In Proff you enter the U-value for each building component in the model you draw. For ground floors, Proff works out the equivalent U-value under NS-EN ISO 13370, and that value is used in the calculation and in the energy certificate.
- U-value per building component, entered where you draw it
- Equivalent U-value for ground floors under NS-EN ISO 13370
- Checks against the TEK17 minimum requirements for small houses
Questions and answers
TEK17 requires at most 0.22 W/(m²K) as a minimum. New buildings that need to meet the energy frame are often around 0.15 to 0.18, and passive houses lower still.
Sources and regulations
Always check the current version of regulations and standards before using the numbers in a project.
Read next
Energy requirements in TEK17
Energy frames per building category, minimum requirements and how compliance is documented.
Passive house calculation: NS 3700 and NS 3701
The criteria for passive houses and low-energy buildings, and how they are documented.
NS 3031:2025 and energy performance calculation
The standard every Norwegian energy calculation is built on, and what is new in the 2025 edition.
Spend your time on judgment, not data entry
Proff gathers available building data, reads floor plans and builds an editable model, so you can calculate everything from houses to hospitals without the detours.