U-value: calculating heat loss in components

The U-value tells you how much heat passes through one square meter of a building component when there is one degree of difference between inside and outside. The lower the U-value, the better the construction insulates. It is one of the most important inputs in any energy calculation.

How to calculate the U-value

The U-value is the inverse of the total thermal resistance. The thermal resistance of each layer is its thickness divided by the thermal conductivity of the material. Add the internal and external surface resistances. The calculation method is set out in NS-EN ISO 6946.

  • Add up the thermal resistance of each layer, plus the internal and external surface resistance
  • Calculate non-uniform layers, such as insulation between studs, with upper and lower limits
  • Ground floors are calculated under NS-EN ISO 13370, because the ground also insulates
  • Windows and doors have their own U-values from the manufacturer, including the frame

The minimum requirements in TEK17

However the energy frame is met, TEK17 section 14-3 limits how poor individual components can be. The requirements make sure a building does not compensate for weak insulation with an efficient heating system.

Minimum requirements in TEK17 section 14-3

Applies to buildings in general. Homes and holiday homes with log outer walls have separate requirements.

ComponentRequirement
External wallU-value at most 0.22 W/(m²K)
RoofU-value at most 0.18 W/(m²K)
Floor on ground and toward open airU-value at most 0.18 W/(m²K)
Window and door, including frameU-value at most 1.2 W/(m²K)
Air leakage at 50 PaAt most 1.5 air changes per hour

Source: Norwegian Building Authority, TEK17 section 14-3. Check the current text before use.

Thermal bridges come on top

The U-value describes the surface. Where constructions meet, at floor joists, window frames and corners, thermal bridges add extra heat loss. In the energy calculation they are included as a normalized thermal bridge value for the whole building. In a well-insulated building, thermal bridges can make up a large share of the total transmission loss.

How Proff handles it

U-values in the model

In Proff you enter the U-value for each building component in the model you draw. For ground floors, Proff works out the equivalent U-value under NS-EN ISO 13370, and that value is used in the calculation and in the energy certificate.

  • U-value per building component, entered where you draw it
  • Equivalent U-value for ground floors under NS-EN ISO 13370
  • Checks against the TEK17 minimum requirements for small houses
Book a Proff demo

Questions and answers

TEK17 requires at most 0.22 W/(m²K) as a minimum. New buildings that need to meet the energy frame are often around 0.15 to 0.18, and passive houses lower still.

Sources and regulations

Always check the current version of regulations and standards before using the numbers in a project.

Read next

Spend your time on judgment, not data entry

Proff gathers available building data, reads floor plans and builds an editable model, so you can calculate everything from houses to hospitals without the detours.